SCADAPACK 337E Review
SCADAPack 337E is the DNP3/IEC60870 centric Smart RTU
It is a Compact Smart RTU combining capabilities of remote terminal units with the power of Programmable Logic Controller and designed to run in challenging remote environment. Supporting open event-driven protocols such as DNP3 and IEC 60870-5, the SCADAPack 300E range provide a scalable controller platform that ensure end to end reliable and secure control and monitoring of remote asset in critical infrastructure.
Features
Wide range of connectivity: Ethernet IP/Series, integration with long range radios, public networks and satellite systems
Flexible I/O configuration:
- 3 Pulse counter inputs
- 8 Analog Inputs 15 bit resolution
- 16 Digital Inputs
- 10 Relay Outputs
- 2 Analog Outputs (optional)
- I/O can be expanded using external modules
Event logging of critical data: Up 20,000 events (40,000 in case of SP ES) can be logged in the controller’s memory
Enhanced security suite: IEEE1711 encryption & IEC62351 authentication, support of DNP3 level 4
Remote configuration: Remote programming, configuration and diagnostics
Note: Configured using E-Series Configurator tool and programmed using IEC61131 ONLY
SCADAPack IEC 61131-3 Workbench
IEC 61131-3 is the first global standard in control logic programming. By standardizing the control system interface, this programming environment complements the manner in which technicians and engineers design, program, operate and maintain industrial control systems. The IEC 61131-3 software package includes the four main languages:
– Sequential Function Chart (SFC)
– Ladder Diagram (LD)
– Function Block Diagram (FBD)
– Structured Text (ST)The product is available as a software licensed version. It operates in conjunction with the SCADAPack E Configurator software for configuration, maintenance, and diagnosis of the SCADAPack E range of smart RTUs.
Benefits
Smart RTU for Challenging Applications
- Industrial hardened: Designed for remote applications, offers higher degree of reliability and longevity
- Remote communication: Integrates with virtually any communication network including Trio radios and 3G mobile networks
- Optimised for WWW applications: Integrated PLC/RTU, reports to multiple masters, routing between communication ports
- Integrated Security Suite: Supports data encryption and authentication using IEEE1711 and IEC62351 standards
Applications
Water & Wastewater
- Lift/Booster Station for 4 pumps
- Demand billing
Specifications
product or component type | Remote terminal unit |
---|---|
market segment | Oil and gas Water and waste water |
processor name | ARM7 |
memory type | 4 MB SRAM 4 MB CMOS RAM 16 MB NAND flash |
communication port protocol | Modbus RTU Modbus TCP DNP3 level 4 IEC 60870-5-104 IEC 60870-5-101 FTP Telnet DF1 |
---|---|
physical interface | RS232 – location: serial port 1 – communication protocol: TxD, RxD, CTS, RTS, DCD, DTR 115…200 bauds RS232 – location: serial port 2 – communication protocol: TxD, RxD, CTS, RTS, DCD, DTR 115…200 bauds RS485 – 2-wire – location: serial port 1 115…200 bauds RS485 – 2-wire – location: serial port 2 115…200 bauds RS232 – location: serial port 3 – communication protocol: TxD, RxD, CTS, RTS, DCD, DTR 115…200 bauds RJ45 – location: Ethernet port 1 10/100 Mbps |
input type | Digital x32 inputs,, 0…31 V DC Digital x32 inputs,, 12…24 V DC Analog x8 inputs,, 0…5 V DC Analog x8 inputs,, 0…10 V DC |
counting frequency | 1 x 1 x 10 Hz 2 x 10 kHz 2 x |
maximum number of I/O expansion module | 5304.0 for analog output 5405.0 for digital input 5414.0 for digital input 5415.0 for digital output 5506.0 for analog input 5606.0 for expansion I/O 5607.0 for expansion I/O |
power consumption in W | 5.8 W |
net weight | 1.2 kg |
length | 211.8 mm |
width | 181.0 mm |
height | 66.0 mm |
standards | EN/IEC 61131-2 CSA C22.2 No 61010-1-12 CSA C22.2 No 61010-2-201 UL 61010-1 UL 61010-2-020 IEC 61010-2-201 FCC CFR 47 part 15 |
marking | CE RCM |
ambient air temperature for operation | -40…70 °C -40…70 °C |
---|---|
ambient air temperature for storage | -40…85 °C -40…85 °C |
relative humidity | 5…95 % |
pollution degree | 2 |
product certifications | CCSAus CSA ACMA IECEx ATEX II 3g EEx ec nC II T4 Gc FCC part 15 class A |
Download Product Datasheet
Related Items
Expansion Modules
- Cables
Radio Transceivers
– Module 5908 – Wireless Data Transceiver
– Avalaible in 900 MHz and 2.4 GHz versions
– Long range (60 miles with 900 MHz models)
– High speed (115.2 Kbps true data throughput)
– Incorporates Freewave Radio Technology
– cCSAus and cULus Class I, Division 2 Hazardous Area Rating
– UL508 listed
Part Number : TBUX297270
Module 5908 – WO2 – Wireless Data Transceiver
– High Speed (115.2 kbps true data throughput)
– Incorporates MDS Radio Technology
– Store and Forward – with self healing network
– Unlimited repeater stations
– Sleep Mode – ideal for solar power applications
– cCSAus and cULus Class I, Division 2 Hazardous Area Rating
– UL508 listed
Part Number : TBUX297310
Ethernet Switch
Module 5910 – Ethernet Switch
– 5-port, 10/100BaseT Ethernet switch
– Auto MDI/MDI-X crossover operation
– Powered by SCADAPack 5V source
– cCSAus and cULus Class I, Division 2 Hazardous Area Rating
– UL508 listed
Part Number: TBUX297288
Part Number: TBUX297289, Module 5910SA (5910 module with 115Vac AC adapter for connection to PC’s or other RS-232 devices)
Modem and Interface Modules
Module 5904 – HART Interface Module
– Compliant with HART physical layers specifications
– Configurable as primary or secondary master
– Unloads HART protocol details from application software
– Enables up to 4 HART ports per CPU without using CPU serial ports
– cCSAus and cULus Class I, Division 2 Hazardous Area Rating
– UL508 listed
Part Number: TBUX297205
Module 5902 – Bell 202 Radio or Leased Line Modem
– Universal radio or telephone interface
– Soft carrier turnoff for rapid turn-around
– Excellent performance on poor lines
– Optional stand-alone versions for PCs
– cCSAus and cULus Class I, Division 2 Hazardous Area Rating
– UL508 listed
Part Number: TBUX297120
Part Number: TBUX297194, Module 5902SA (5902 module with 115Vac AC adapter for connection to PC’s or other RS-232 devices, DE9S port)
Part Number: TBUX297195, Module 5902SAF (5902SA module with Full Duplex support, for use with devices with no RTS/CTS support)
Module 5915 – SDI-12 Interface Module
– RS232 to SDI-12 hardware interface
– Supported by SCADAPack 32 & 300 Series controllers
– C++ application provides SDI-12 protocol functionality *
– Companion TelePACE or ISaGRAF application generates protocol messages *
– External (RJ45) RS232 connection to SCADAPack com port
– Powered by external 12V source
– Class I, Division 2 Groups A, B, C and D Hazardous Locations
– CSA certified to UL508 standards
– UL508 listed
– ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2)
Part Number: TBUX297475
Bluetooth Interface
Local Wireless Connectivity
Bluetooth® is a global standard communications method that enables data to be exchanged wirelessly between electronic devices. The 5913 and 5914 BluetoothInterface products are designed to provide wireless connection between SCADAPack controllers and PCs. This wireless connection replaces direct serial connections, which are difficult to create in many field installations.
Features of the 5913 & 5914 include:
– Wireless communications module certified to Bluetooth® version 2.0
– Bluetooth Class 1: +100 meter (330 feet) distance when communicating with another Class 1 device
– Serial port (UART) baud rate speeds: 1200bps up to 921.6Kbps
– PCB antenna
– Secure and robust communication link
– 2.402 to 2.48 GHz FHSS (Frequency Hopping Spread Spectrum) radio modem
– Encryption and 16-character alphanumeric Personal Identification Number (PIN) and error correction schemes for guaranteed packet delivery
– C(CSA) US
5913 Serial to BluetoothAdapter
– Acts as Bluetooth slave
– Connects to SCADAPack 300E RJ-45 serial port connector, (cable included)
– Wireless communications module certified to Bluetooth® version 2.0
– Bluetooth Class 1: +100 meter (330 feet) distance when communicating with another Class 1 device
– Encryption and 16-character alphanumeric
– Personal Identification Number (PIN) and error correction schemes for guaranteed packet delivery
– Part Number: TBUX297373
5914 USB to BluetoothTransceiver
– Acts as Bluetooth master
– Connects to USB port on desktop or laptop computer
– Wireless communications module certified to Bluetooth® version 2.0
– Bluetooth Class 1: +100 meter (330 feet) distance when communicating with another Class 1 device
– Encryption and 16-character alphanumeric
– Personal Identification Number (PIN) and error correction schemes for guaranteed packet delivery
Part Number: TBUX297374
Communication Modules
- Analog I/O
Module 5304 – Analog Output Module- Selectable voltage and current modes
- 5V and 10V selectable voltage modes
- Low power
- cCSAus and cULus Class I, Division 2 Hazardous Area Rating
- UL508 listed
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2)
Module 5505 – RTD Input Module- Input values scaled and linearized
- Data returned as 32-bit floating-point number
- Lower power consumption
- Automatic 3-wire RTD compensation
- 5503 emulation mode for legacy systems
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2)
- UL508 listed
Module 5506 – Analog Input Module- 8 channel isolated
- 0 to 20mA / 4 to 20mA inputs
- 0 to 5V / 1 to 5V inputs
- Individual input configuration
- 5501 emulation mode for legacy systems
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2)
- UL Listed
Digital I/O
Module 5405 – Digital Input Module- High density, 32 digital inputs
- Sinking input design
- Low power
- cCSAus and cULus Class I, Division 2 Hazardous Area Rating
- UL508 listed
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2)
Part Number: TBUX297247 (5405-24, 24V discrete input module)
Module 5411 – Digital Output Module- High density, 32 digital outputs
- Sinking output design
- Low power
- cCSAus and cULus Class I, Division 2 Hazardous Area Rating
- UL508 listed
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2)
Module 5414 – Compact Digital Input Module- 16 optically-isolated digital inputs
- 12 to 240 volts
- Universal AC or DC
- Very low power requirements
- Compact module
- Class I, Division 2 Groups A, B, C and D Hazardous Locations
- CSA certified to UL508 standards
- UL508 listed
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2) (5414-24 only)
Part Number: TBUX297378 (5414-24, 24V AC/DC, compact discrete input module) Note: Not supported by 16-bit SCADAPack controllers
Module 5415 – Compact Relay Digital Output Module- 12 relay digital outputs
- Dry Contact or Solid State Relay versions
- Isolated in 3 groups of 4
- Very low power requirements
- Compact module
- Class I, Division 2 Groups A, B, C and D Hazardous Locations
- CSA certified to UL508 standards
- UL508 listed
- ATEX ll 3G and IECEx: Ex nA llC per EN 60079-15, protection type n (Zone 2) , (5415-A only)
Part Number: TBUX297384 (5415-A, Certified to ATEX)
Combination I/O
Module 5606 – Analog/Digital I/O Module- High density IO combination board
- 32 Digital Inputs
- 16 Relay Digital Outputs
- 8 Configurable Analog Inputs
- Optional Analog Outputs
- Up to 8 modules supported
- cCSAus and cULus Class I, Division 2 Hazardous Area Rating
- UL508 listed
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2), (24VDI/Solid State Relay type only)
Part Number: TBUX297330 (5606-120, 32 D/I 120 volts)
Part Number: TBUX297334 (5606-24-AO, 32 D/I 12-24 volts)
Part Number: TBUX297336 (5606-120-AO, 32 D/I 120 volts)
Part Number: TBUX297498 (5606-24-A, 32 D/I 12-24 volts)
Part Number: TBUX297500 (5606-120-A, 32 D/I 120 volts)
Part Number: TBUX297502 (5606-24-AO-A, 32 D/I 12-24 volts)
Part Number: TBUX297504 (5606-120-AO-A, 32 D/I 120 volts)
Module 5607 – Analog/Digital I/O Module- High density IO combination board
- 16 Digital Inputs
- 10 Relay Digital Outputs (Dry Contact or Solid State versions)
- 8 Configurable Analog Inputs
- Optional Analog Outputs
- Up to 8 modules supported
- Class I, Division 2 Groups A, B, C and D Hazardous Locations
- CSA certified to UL508 standards
- ATEX ll 3G and IECEx: Ex nA llC T4 per EN 60079-15, protection type n (Zone 2), (24VDI/Solid State Relay type only)
TBUX297480 (5607-120, 16 D/I 120 volts)
TBUX297482 (5607-24-AO, 16 D/I 12-24 volts)
TBUX297484 (5607-120-AO, 16 D/I 120 volts)
TBUX297490 (5607-24-A, 16 D/I 12-24 volts)
TBUX297492 (5607-120-A, 16 D/I 120 volts)
TBUX297494 (5607-24-AO-A, 16 D/I 12-24 volts)
TBUX297496 (5607-120-AO-A, 16 D/I 120 volts)
Cables
Intermodule cables
TBUM297269 Shielded intermodule cable, 12 inches (0.3m) long
TBUM297192 Shielded intermodule cable, 18 inches (0.45m) long
TBUM297193 Shielded intermodule cable, 24 inches (0.61m) long
TBUM297192 Shielded intermodule cable, 18 inches (0.45m) long
TBUM297131 Shielded intermodule cable, 30 inches (0.76m) long
TBUM297162 Shielded intermodule cable, 45 inches (1.14m) long
TBUM297174 Shielded intermodule cable, 72 inches (1.82m) long
TBUM297162 Shielded intermodule cable, 45 inches (1.14m) long
ES & ER Specific Cables
TBUM297358 RS-232 Cable, RJ12 to RJ45, Null Modem, 3 feet (0.91m)
TBUM297357 RS-232 Cable, RJ12 to DE9P, Straight, 3 feet (0.91m)
TBUM297324 RS-232 Cable, RJ12 to DE9S (Female), Null Modem (Tx, Rx, Gnd), 10ft (3.05m)
Serial Cables
TBUM297820 Communication Cable, DE9P to DE9S, 3 wires (Tx,Rx,Gnd), 10ft (3.05m)
TBUM297821 Communication Cable, DE9P to RJ45, 3 wires (Tx,Rx,Gnd), 10ft (3.05m)
TBUM297488 Communication Cable, Port B to DE9S (Tx,Rx,Gnd), 10 ft. (3.05m)
TBUM297824 Communication Cable, RJ45 to DE9S, 3 wires (Tx,Rx,Gnd), 10ft (3.05m)
TBUM297822 Communication Cable, RJ45 to RJ45, 3 wires (Tx,Rx,Gnd), 10ft (3.05m)
TBUM297816 Programming Cable, RJ45 (Male) to DE9S (Female), 6.5 feet (2m)
TBUM297449 RS-232 Cable, DE9S to DE9P (Tx,Rx,RTS,CTS,GND,5v), Straight, 1 ft. (0.3m)
TBUM294055 RS-232 Cable, DE9S to DE9S (9 Pin Female to 9 Pin Female) – Null Modem, 6 feet (1.82m)
TBUM297234 RS-232 Cable, RJ45 to 8 Stripped wires (Tx, Rx, RTS, CTS, DTR, DCD, GND, 5v), no connector, 10 feet (3.05m)
TBUM297218 RS-232 Cable, RJ45 to DE9P (Male), 8 wires (Tx, Rx, RTS, CTS, DTR, DCD, GND, 5v) – Straight, 15 inches (0.38m)
TBUM297217 RS-232 Cable, RJ45 to DE9S (Female), 3 wires (Tx, Rx, Gnd) – Null Modem, 10 feet (3.05m)
TBUM297304 RS-232 Cable, RJ45 to DE9S (Female), 6 wires (Tx, Rx, RTS, CTS, Gnd, 5v) – Null Modem, 2 feet (0.61m)
TBUM297448 RS-232 Cable, RJ45 to RJ45 (Tx,Rx,RTS,CTS,GND,5v), Null Modem, 1 ft. (0.3m)
TBUM297303 RS-232 Cable, RJ45 to RJ45, 6 wires (Tx, Rx, RTS, CTS, Gnd, 5v) – Null Modem, 2 feet (0.61m)
Ethernet Cables
TBUM297244 Ethernet Cable, RJ45 to RJ45, 3 feet (0.91m)
TBUM297245 Ethernet Cable, RJ45 to RJ45, 6 feet (0.82m)
USB Cables
TBUM297332 USB Cable, High Speed USB 2.0 Cable, 10 feet (3.05m)
TBUM297333 USB Cable, High Speed USB 2.0 Cable, 15 feet (4.57m)
Fuse and Connector Kits
Fuse Kits for SCADAPack E Controllers
TBUM297327 Fuse Kit for SCADAPack 300 and 300E Series controllers, contains 10 fuses, Nano-SMF, 1.5 A, Fast Blow
Fuse Kits for SCADAPack ES Controllers
TBUM297181 Fuse Kit for SCADAPack ES CPU module
TBUM297182 Fuse Kit for SCADAPack ES I/O module
TBUM297183 Fuse Kit for SCADAPack ES auxiliary 5 volt power supply module
TBUM297184 Fuse Kit for SCADAPack ES auxiliary 10 volt and 24 volt power supply module
Connector Kits for SCADAPack E Controllers
TBUM297262 SCADAPack Series Connector Kit for 2 pin Terminal Block, contains five of the 2 Pin connectors
TBUM297290 SCADAPack Series Connector Kit for 4 pin Terminal Block, contains five of the 4 Pin connectors
TBUM297291 SCADAPack Series Connector Kit for 5 pin Terminal Block, contains five of the 5 Pin connectors
TBUM297263 SCADAPack Series Connector Kit for 6 pin Terminal Block, contains five of the 6 Pin connectors
TBUM297264 SCADAPack Series Connector Kit for 8 pin Terminal Block, contains five of the 8 Pin connectors
TBUM297265 SCADAPack Series Connector Kit for 9 pin Terminal Block, contains five of the 9 Pin connectors
TBUM297266 SCADAPack Series Connector Kit for 10 pin Terminal Block, contains five of the 10 Pin connectors
TBUM297321 SCADAPack Series Connector Kit for 11 pin Terminal Block, contains five of the 11 Pin connectors
TBUM297267 SCADAPack Series Connector Kit for 12 pin Terminal Block, contains five of the 12 Pin connectors
Connector Kits for SCADAPack ES Controllers
TBUM297460 SCADAPack ES Series Connector Kit for 2 pin Terminal Block, contains five of the 2 Pin connectors
TBUM297461 SCADAPack ES Series Connector Kit for 3 pin Terminal Block, contains five of the 3 Pin connectors
TBUM297462 SCADAPack ES Series Connector Kit for 4 pin Terminal Block, contains five of the 4 Pin connectors
TBUM297463 SCADAPack ES Series Connector Kit for 5 pin Terminal Block, contains five of the 5 Pin connectors
Operator Interface Terminal
The SCADAPack Vision family of operator interface terminals are multi-purpose devices that provide local display of controller process variables and operator-input of any control parameter. Two models are available, the SCADAPack Vision10 and SCADAPack Vision60, each offering varying LCD size, keypad and screen memory configurations. A companion software application furnishes all the necessary tools for easily configuring the units.
With five times the screen configuration memory of the Vision10, the SCADAPack Vision60 is the ideal choice for applications requiring a large number of display screens and data display functions. Expanded memory increases the alarm capacity to 256 alarms, making the Vision60 a compact yet powerful manager for local alarms. Additionally, the Vision60 can display data in ASCII format.
All SCADAPack Vision products feature a NEMA4 faceplate for panel mounting and a backlit display for easy reading in dim light conditions. These HMI devices use Modbus protocol to communicate with the SCADAPack, and are therefore compatible with other Modbus protocol-equipped PLCs.
For outdoor installations of SCADAPack Vision units, our company offers the Vision Shield. This rugged, easy-to-install shield will protect keypads from the environment, including UV rays. The Vision Shield must accompany any Vision unit installed outdoors in order to maintain the product warranty.
Miscellaneous
Transformers & Batteries
TBUM294034 12V, 6AH battery for use with model 5103 power supply
TBUM295003 60 Hz mains transformer 120V to 16V @ 20 VA
TBUM295027 50 Hz mains transformer 220-240V to 16V @ 20 VA
TBUM294000 60Hz mains transformer 120V to 24V @ 40 VA, for use with 5103
TBUM294167 60Hz mains transformer 240V to 24V @ 40VA, for use with 5103
TBUM297268 Battery Kit, contains 3 Lithium 3.6 Volt button type batteries for RAM retention
TBUM297456 Battery Kit, contains 3 Lithium 3.6 Volt button type batteries for RAM retention (China)
Field Activated Licenses
TBUM327036 DF1 Protocol License for SCADAPack 32 and 300 Series Controllers
TBUM297453 DNP3 Data Concentrator License for SCADAPack E Controllers
TBUM297867 IEC 60870-5-103 Master License for SCADAPack E Controllers
TBUM297472 AGA-12 Encryption Security License for SCADAPack E Controllers
TBUM297856 Secure Authentication License for SCADAPack E Controllers
Memory Cards for SCADAPack ES Controllers
TBUM297353 Compact FLASH card, 2GB
TBUM297486 Compact FLASH card, 4GB